Fault
code
on the
display
Const.
weath.-
comp.
System char-
acteristics
Cause
Measures
dd
X
Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit A1
lead broken
Check the room
temperature sen-
sor, heating cir-
cuit A1 and the
remote control
DIP switch set-
tings (see
page 114)
dE
X
Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit
with mixer
M2 lead bro-
ken
Check the room
temperature sen-
sor, heating cir-
cuit with mixer M2
and the remote
control DIP switch
settings (see
page 114)
E4
X
X
Burner
blocked
Fault, supply
voltage 24 V
Replace the con-
trol unit.
E5
X
X
Burner
blocked
Fault
–
flame
amplifier
Replace the con-
trol unit.
E6
X
X
Burner
blocked
System
pressure too
low
Top up with water.
E8
X
X
Burner in a
fault state
The ionisa-
tion current
lies outside
the permissi-
ble range
Check the ionisa-
tion electrode and
cable.
Press "
E
RESET".
E9
X
X
Burner in a
fault state
The ionisa-
tion current
lies outside
the permissi-
ble range
during cali-
bration
Check the ionisa-
tion electrode and
cable.
Check the flue
gas system for
tightness.
Press "
E
RESET".
Fault codes
(cont.)
83
Troubleshooting
56
92
682
GB
Summary of Contents for Vitodens 333-F
Page 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Page 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Page 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Page 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Page 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Page 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Page 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Page 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...