System version 5
One heating circuit with mixer M1 (with Vitotronic 200-H), one heating cir-
cuit with mixer M2 (with extension kit) and low loss header (with/without
DHW heating)
1
Vitodens 333-F
2
Outside temperature sensor
3
Heating circuit with mixer M1
4
Flow temperature sensor M1
5
Heating circuit pump M1
6
Vitotronic 200-H
7
Heating circuit with mixer M2
8
Temperature limiter for limiting the
max. temp. of underfloor heating
systems
9
Flow temperature sensor M2
qP
Heating circuit pump M2
Extension kit for one heating cir-
cuit with mixer M2
qW
Low loss header
qE
Flow temperature sensor, low loss
header
Required coding
Operation with LPG
82:1
System with only one heating circuit with mixer and DHW heating
00:4
Further details regarding the individual steps
(cont.)
37
Commissioning, inspection, maintenance
56
92
682
GB