Fault
code
on the
display
Const.
weath.-
comp.
System char-
acteristics
Cause
Measures
C7
X
X
Control mode,
max. pump
speed
Communica-
tion fault
–
external vari-
able speed
heating cir-
cuit pump,
heating
circuit A1
Check setting of
coding address
"E5"
Cd
X
X
Control mode
Communica-
tion fault
Vitocom 100
(KM BUS)
Check connec-
tions, Vitocom 100
and coding ad-
dress "95"
CE
X
X
Control mode
Communica-
tion fault
–
ext. exten-
sion
Check connec-
tions and coding
address "2E"
CF
X
Control mode
Communica-
tion fault,
LON com-
munication
module
Replace the LON
communication
module
dA
X
Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit A1
shorted out
Check the room
temperature sen-
sor, heating cir-
cuit A1
db
X
Control mode
without room
influence
Room tem-
perature
sensor, heat-
ing circuit
with mixer
M2 shorted
out
Check the room
temperature sen-
sor, heating cir-
cuit with mixer M2
Fault codes
(cont.)
82
Troubleshooting
56
92
682
GB
Summary of Contents for Vitodens 333-F
Page 5: ...Keyword index 133 Index cont 5 Index 5692 682 GB ...
Page 123: ...Parts lists cont 123 Parts lists 5692 682 GB ...
Page 124: ...Parts lists cont 124 Parts lists 5692 682 GB ...
Page 125: ...Parts lists cont 125 Parts lists 5692 682 GB ...
Page 126: ...Parts lists cont 126 Parts lists 5692 682 GB ...
Page 127: ...Parts lists cont 127 Parts lists 5692 682 GB ...
Page 128: ...Parts lists cont 128 Parts lists 5692 682 GB ...
Page 135: ...Keyword index cont 135 Keyword index 5692 682 GB ...