90
Weather-compensated control unit
Constant temperature control unit
Resetting all codes to their delivered condition
Select
"Standard setting"
.
Note
This also resets codes at coding level 1.
Select
"7"
with
Ú
and confirm with
OK
.
When
" "
flashes, confirm with
OK
.
Note
This also resets codes at coding level 1.
"General"/group 1
Select
"General"
for weather-compen-
sated control units (see page 89).
Select
"1"
for constant temperature con-
trol units (see page 89).
Coding
Coding in the delivered condition
Possible change
00:2
One heating circuit with-
out mixer A1 (heating cir-
cuit 1)
00:4
to
00:10
For system schemes, see
the following table:
Value ad-
dress
00: ...
Description
2
One heating circuit without mixer A1 (heating circuit 1) (code is set au-
tomatically)
4
One heating circuit with mixer M2 (heating circuit 2)
6
One heating circuit without mixer A1 (heating circuit 1)
One heating circuit with mixer M2 (heating circuit 2)
(code is set automatically)
8
One heating circuit with mixer M2 (heating circuit 2)
One heating circuit with mixer M3 (heating circuit 3)
10
One heating circuit without mixer A1 (heating circuit 1)
Two heating circuits with mixer M2 (heating circuit 2) and M3 (heating
circuit 3)
(code is set automatically)
Code 2
Calling up coding level 2
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...