57
1.
Remove cover
A
.
2.
Remove earth cable
B
from tab
C
.
3.
Connect tester (up to 5 mA ) in series
between tab
C
and earth cable
B
.
■ If the current measures > 0.3 mA,
the anode is OK.
■ If the current measures < 0.3 mA or
if there is no current at all, inspect
the anode visually (see page 60).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5773 216 GB
Service