108
Coding in the delivered condition
Possible change
Minimum speed of the in-
ternal variable speed
heating circuit pump in
operation with reduced
room temperature sub-
ject to the setting in cod-
ing address "E9" (only for
weather-compensated
control units)
E9:45
Only for heating systems
without a heating circuit
with mixer:
Speed of the internal var-
iable speed heating cir-
cuit pump:
45 % of the max. speed
during operation with re-
duced room temperature
(only for weather-com-
pensated control units)
E9:0
to
E9:100
Speed adjustable from 0 to
100 % of the maximum
speed during operation
with reduced room temper-
ature
F1:0
Screed drying disabled
(only for weather-com-
pensated control units)
F1:1
to
F1:6
Only for heating circuit with
mixer:
Screed drying adjustable in
accordance with 6 selecta-
ble temperature/time pro-
files (see page 161)
F1:15
Constant flow temperature
20 °C
F2:8
Time limit for party mode
or external heating pro-
gram changeover via
pushbutton: 8 h (only for
weather-compensated
control units)
*1
F2:0
No time limit for party
mode
*1
F2:1
to
Time limit adjustable from 1
to 12 h
*1
*1
In the "Heating and DHW" program, party mode ends automatically when the
system changes over to operation with standard room temperature.
Code 2
"Heating circuit ..."/group 5
(cont.)
5773 216 GB
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...