
81
Coding in the delivered condition
Possible change
Service interval in months
23:0
No interval for burner
service
23:1
to
23:24
Interval adjustable from 1
to 24 months
Service status
24:0
"Service"
not shown on
display
24:1
"Service"
is shown on dis-
play (the address is auto-
matically set and must be
manually reset after a serv-
ice has been carried out)
Filling/Venting
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
"DHW"/group 3
Select
"DHW"
for weather-compensa-
ted control units (see page 77).
Select
"3"
for constant temperature con-
trol units (see page 77).
Coding
Coding in the delivered condition
Possible change
Enable DHW circulation pump
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:1
to
73:6
During time program
"ON" from once per hour
for 5 min to
"ON" 6 times per hour for
5 min
73:7
Constantly "ON"
"Heating circuit ..."/group 5
Select
"Heating circuit ..."
for weather-
compensated control units (see
page 77).
Select
"5"
for constant temperature con-
trol units (see page 77).
Code 1
"Boiler"/group 2
(cont.)
5773 216 GB
Service
Summary of Contents for Vitodens 222-F B2TA series
Page 12: ...12 2 5 1 4 2x 3 Installing the boiler Removing the front panels 5773 216 GB...
Page 13: ...13 1 2 SW17 Installing the boiler Siting and levelling the boiler 5773 216 GB Installation...
Page 31: ...31 4 1 5 2 2x 3 Installing the boiler Fitting the front panels 5773 216 GB Installation...
Page 194: ...194 5773 216 GB...
Page 195: ...195 5773 216 GB...