Coding in the delivered condition
Possible change
11:
≠
9
No access to the coding
addresses for the para-
meters of the combus-
tion controller
11:9
Access open to the cod-
ing addresses for the
parameters of the com-
bustion controller
21:0
No maintenance inter-
val (operating hours)
selected
21:1
to
21:9999
The number of hours run
before the burner should
be serviced is adjustable
from 1 to 9999 h
23:0
No time interval for
burner service selected
23:1
to
23:24
Interval adjustable from 1
to 24 months
24:0
The service display is
reset
24:1
Service display (value
displayed automatically)
25:0
i
: No outside tem-
perature sensor or re-
mote monitoring
recognised (only for
constant temperature
control units)
25:1
Outside temperature sen-
sor and fault monitoring
recognised
28:0
No burner interval igni-
tion
28:1
to
28:24
Time interval adjustable
from 1 to 24 h. The burn-
er is force-started re-
spectively for 30s.
2E:0
Without external exten-
sion
2E:1
With external extension
(automatic setting on
connection)
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
30:1
Variable speed circula-
tion pump in the heating
circuit connection set
(automatic adjustment)
30:0
Circulation pump in the
heating circuit connection
set, without variable
speed (e.g. temporarily
for service)
31:...
Set speed of the circu-
lation pump in the heat-
ing circuit connection
set, when operated as
boiler circuit pump in %,
defaulted by the boiler
coding card
31:0
to
31:100
Set speed adjustable
from 0 to 100 %
Code 2
(cont.)
42
Coding
5692
761
GB