Coding in the delivered condition
Possible change
32:0
Influence of the signal
"External blocking" on
circulation pumps: All
pumps in control func-
tion
32:1
to
32:15
Influence of the signal
"External blocking" on
circulation pumps: see
the following table
Note
Generally, the burner will be blocked when signal "External blocking" is
enabled.
Value
address
32: ...
Circulation
pump in the
heating circuit
connection
set
Heating circuit
pump
Heating circuit
without mixer
Heating circuit
pump
Heating circuit
with mixer
Cylinder pri-
mary pump
0
Control funct.
Control funct.
Control funct.
Control funct.
1
Control funct.
Control funct.
Control funct.
OFF
2
Control funct.
Control funct.
OFF
Control funct.
3
Control funct.
Control funct.
OFF
OFF
4
Control funct.
OFF
Control funct.
Control funct.
5
Control funct.
OFF
Control funct.
OFF
6
Control funct.
OFF
OFF
Control funct.
7
Control funct.
OFF
OFF
OFF
8
OFF
Control funct.
Control funct.
Control funct.
9
OFF
Control funct.
Control funct.
OFF
10
OFF
Control funct.
OFF
Control funct.
11
OFF
Control funct.
OFF
OFF
12
OFF
OFF
Control funct.
Control funct.
13
OFF
OFF
Control funct.
OFF
14
OFF
OFF
OFF
Control funct.
15
OFF
OFF
OFF
OFF
Coding in the delivered condition
Possible change
Boiler/burner
34:0
Influence of the signal
"External demand" on
the circulation pumps:
All pumps in control
function
34:1
to
34:23
Influence of the signal
"External demand" on the
circulation pumps: see
the following table
Code 2
(cont.)
43
Coding
5692
761
GB