1.
Switch OFF the main power supply
and the ON/OFF switch at the con-
trol unit.
2.
Close the gas shut-off valve and
safeguard against reopening.
3.
Unlock control unit
A
and pivot
forwards.
4.
Remove cover panel
B
.
5.
Pull cables from fan motor
C
, gas
train
D
, ignition unit
E
, earth tab
F
and ionisation electrode
G
.
6.
Release gas supply pipe fittings
H
.
7.
Undo six screws
K
and remove
the burner.
8.
Check burner gasket
L
for
damage. Replace gasket, if
required.
Further details regarding the individual steps
(cont.)
18
Commissioning, inspection, maintenance
5692
761
GB