Checking the outside temperature sensor (weather-compen-
sated control unit)
1.
Pull plug "X3" from the control unit.
2.
Test the resistance of the outside
temperature sensor across term-
inals "X3.1" and "X3.2" on the dis-
connected plug and compare it with
the curve.
3.
Where actual values strongly devi-
ate from the curve values, discon-
nect the wires at the sensor and
repeat test immediately at the sen-
sor.
4.
Subject to result, replace the lead
or the outside temperature sensor.
Repairs
81
Troubleshooting
5692