Coding in the delivered condition
Possible change
Slope A1/M2
d3:14
Heating curve slope =
1.4 (only for weather-
compensated control
units)
d3:2
to
d3:35
Heating curve slope ad-
justable from 0.2 to 3.5
(see page 29)
Level A1/M2
d4:0
Heating curve level = 0
(only for weather-com-
pensated control units)
d4:
–
13
to
d4:40
Heating curve level ad-
justable from
–
13 to 40
(see page 29)
Code 2
Calling up code 2
Note
&
On weather-compensated control
units, codes are displayed as plain
text.
&
Codes that are irrelevant due to the
system equipment level or the set-
ting of other codes will not be dis-
played.
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
d
to confirm.
3.
a
/
b
for the required coding
address; the address
flashes.
4.
d
to confirm; the value
flashes.
5.
a
/
b
for the selected value.
6.
d
to confirm; the display
briefly shows
"
accepted
" (for
weather-compensated
control units); the
address flashes again.
7.
a
/
b
for the selection of
further addresses.
8.
L
+
G
press simultaneously for
approx. 1 s; code 2 is
terminated.
The coding addresses are grouped
according to the following
function
areas
. The respective function area is
shown on the display.
The areas are scanned in the follow-
ing sequence with
a
/
b
:
Code 1
(cont.)
39
Coding
5692
761
GB
Summary of Contents for Vitodens 200-W WB2B Series
Page 109: ...Parts lists cont 109 Parts lists 5692 761 GB...
Page 110: ...Parts lists cont 110 Parts lists 5692 761 GB...
Page 111: ...Parts lists cont 111 Parts lists 5692 761 GB...
Page 118: ...118 5692 761 GB...
Page 119: ...119 5692 761 GB...