25
Minimum room height
1904
> a
A
B
Fig. 17
A
Indoor unit
B
Finished floor level or top edge of platform for
unfinished floors
Minimum room height a depends on the hydraulic con-
nection set used.
Hydraulic connection set
Minimum
room height a
in mm
■
For installation on finished walls, for
upward connection
2200
■
For installation to the left or right on
finished walls
2000
Note
If applicable, remove the packaging box upwards
before installation.
Pressure points
b
Ø d
c
a
Fig. 18
A
Partition joint with edge insulation strip as part of
the floor construction
a
439 mm
b
506 mm
c
670 mm
d
64 mm
Note
■
Observe the permissible floor load.
■
Level the appliance horizontally.
■
If the adjustable feet are used to compensate for an
uneven floor (max. 10 mm), distribute the pressure
load on the individual feet evenly.
The total weight with filled DHW cylinder is 384 kg.
Each pressure point (each with an area of 3217 mm
2
)
is subject to a load of up to 96 kg.
Installation sequence
Installing the indoor unit
(cont.)
5831412
Installation