134
Cooling
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Cooling function
7100
0
Cooling circuit
7101
1
Set room temperature separate cooling cir-
cuit
7102
200 (
≙
20 °C)
Min. flow temperature cooling
7103
200 (
≙
20 °C)
Influence room temperature hook-up cooling
circuit
7104
0
Room temperature control cooling circuit
7105
1
Ranking room temp sensor separate cooling
circuit
7106
0
Hysteresis room temp cooling circuit
7107
10 (
≙
1 K)
Enable flow temperature sensor cooling cir-
cuit
7109
1
Cooling curve level
7110
0 (
≙
0 K)
Cooling curve slope
7111
12 (
≙
1.2)
Remote control cooling circ
7116
Do not adjust.
Dew point monitor
7117
1
Enable active cooling
71FE
0
Ventilation: Vitovent 200-C and Vitovent 300-F
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Vitovent enable
7D00
0
Enable preheater bank electric
7D01
0
Enable reheater bank hydraulic
7D02
0
Enable humidity sensor
7D05
0
Enable CO2 sensor
7D06
0
Set room temperature
7D08
200 (
≙
20 °C)
Flow rate reduced ventilation
7D0A
■
Vitovent 200-C:
75 m
3
/h
■
Vitovent 300-F:
120 m
3
/h
Flow rate nominal ventilation
7D0B
■
Vitovent 200-C:
115 m
3
/h
■
Vitovent 300-F:
170 m
3
/h
Flow rate intensive ventilation
7D0C
■
Vitovent 200-C:
155 m
3
/h
■
Vitovent 300-F:
215 m
3
/h
Min. supply air temperature for bypass
7D0F
160 (
≙
16 °C)
CO2 value for raising the flow rate
7D18
800 ppm
Humidity value for raising the flow rate
7D19
65 %
Interval time frost protection ventilation
7D1A
15 min
Intensive ventilation duration
7D1B
120 min
Actual source room temperature
7D1D
1
Heating circuit for blocking bypass damper
7D21
7
Commissioning/service reports
Control parameter report
(cont.)
5831412
Appendix