140
Type AWOT-M-E/AWOT-M-E-AC
221.A04
221.A06
221.A08
221.A10
221.A13
221.A16
Air intake temperature
Cooling mode (type
AWOT-M-E-AC only)
■
Min.
°C
10
10
10
10
10
10
■
Max.
°C
45
45
45
45
45
45
Heating mode
■
Min.
°C
–
20
–
20
–
20
–
20
–
20
–
20
■
Max.
°C
35
35
35
35
35
35
Heating water
(secondary cir-
cuit)
Minimum flow rate
l/h
700
700
700
1400
1400
1400
Minimum volume in the heating
system, cannot be fitted with
shut-off devices
l
50/40
*3
50/40
*3
50/40
*3
50/40
*3
50/40
*3
50/40
*3
Max. external pressure drop
(RFH) at minimum flow rate
mbar
705
705
705
500
500
500
kPa
70.5
70.5
70.5
50
50
50
Max. flow temperature
°C
60
60
60
60
60
60
Outdoor unit electrical values
Rated voltage, compressor
1/N/PE 230 V/50 Hz
Max. operating current, com-
pressor
A
13.0
14.6
14.6
19.9
23.3
23.3
Cos
ϕ
0.99
0.99
0.99
0.99
0.99
0.99
Starting current, compressor
A
15
15
15
15
15
15
Fuse rating
A
16
16
16
25
25
25
IP rating
IPX4
IPX4
IPX4
IPX4
IPX4
IPX4
Indoor unit electrical values
Heat pump control unit/PCB
■
Rated voltage, control
unit/PCB
1/N/PE 230 V/50 Hz
■
Power supply fuse rating
1 x B16A
■
Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water
heater
■
Rated voltage
1/N/PE 230 V/50 Hz
or
3/N/PE 400 V/50 Hz
■
Heating output
kW
9
■
Power supply fuse rating
3 x B16A
Max. power consumption
Fan
W
45
45
115
2 x 45
2 x 45
2 x 45
Outdoor unit
kW
2.85
3.20
3.30
4.55
5.08
5.08
Secondary pump (PWM)
W
60
60
60
60
60
60
■
Energy efficiency index EEI
≤
0.2
≤
0.2
≤
0.2
≤
0.2
≤
0.2
≤
0.2
Control unit/PCB, outdoor unit
W
15
15
15
15
15
15
Control unit/PCB, indoor unit
W
10
10
10
10
10
10
Control unit/PCB power, indoor
unit
W
1000
1000
1000
1000
1000
1000
*3
When using the heating water buffer cylinder Vitocell 100-E, type SVPA, part no. ZK03801 in the secondary circuit return
Specification
Specification
(cont.)
5831412