133
Heating circuit 2
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
Standard room temperature
3000
200 (
≙
20 °C)
Reduced room temperature
3001
160 (
≙
16 °C)
Remote control
3003
0
Room temperature control
3005
0
Heating curve level
3006
0 (
≙
0 K)
Heating curve slope
3007
6 (
≙
0.6)
Influence room temperature hook-up
300A
10
Room temperature hook-up
300B
0
Max. flow temperature heating circuit
300E
400 (
≙
40 °C)
Runtime mixer heating circ
3015
Do not adjust.
Room temperature in party mode
3022
200 (
≙
20 °C)
Cooling
3030
0
Dew point monitor
3031
1
Min. flow temperature cooling
3033
200 (
≙
20 °C)
Influence room temperature hook-up cooling
circuit
3034
0
Min. actual flow temperature cooling
3036
10 (
≙
1 °C)
Hysteresis room temp cooling circuit
3037
10
Cooling curve level
3040
0
Cooling curve slope
3041
12
Heating circuit 3
Parameter
Code
Factory setting
Commission-
ing
Maintenance/
service
Standard room temperature
4000
200 (
≙
20 °C)
Reduced room temperature
4001
200 (
≙
20 °C)
Remote control
4003
0
Room temperature control
4005
0
Heating curve level
4006
0 (
≙
0 K)
Heating curve slope
4007
6 (
≙
0.6)
Influence room temperature hook-up
400A
10
Room temperature hook-up
400B
0
Max. flow temperature heating circuit
400E
400 (
≙
40 °C)
Runtime mixer heating circ
4015
Do not adjust.
Room temperature in party mode
4022
160 (
≙
16 °C)
Cooling
4030
0
Dew point monitor
4031
1
Min. flow temperature cooling
4033
200 (
≙
20 °C)
Influence room temperature hook-up cooling
circuit
4034
0
Min. actual flow temperature cooling
4036
10 (
≙
1 °C)
Hysteresis room temp cooling circuit
4037
10
Cooling curve level
4040
0
Cooling curve slope
4041
12
Commissioning/service reports
Control parameter report
(cont.)
5831412
Appendix