130
DHW
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
service
Set DHW temperature
6000
500 (
≙
50 °C)
Min. DHW temperature
6005
100 (
≙
10 °C)
Max. DHW temperature
6006
600 (
≙
60 °C)
Hysteresis DHW temperature heat pump
6007
50 (
≙
5 K)
Hysteresis DHW temperature booster heat-
er
6008
100 (
≙
10 K)
Start optimisation for DHW heating
6009
0
Stop optimisation for DHW heating
600A
0
Set DHW temperature 2
600C
600 (
≙
60 °C)
Temperature rise per hour for DHW heating
600D
30 K/h
Max. runtime DHW heating in heating mode 6011
240 (
≙
24 min)
Max. interruption of DHW heating for central
heating
6012
90 (
≙
9 min)
Enable electric heaters for DHW heating
6015
0
Start attempts for DHW after high pressure
shutdown
6017
0
Shutdown hysteresis inst. heating water
heater
601E
10 (
≙
1 K)
Enable elec. heating/ext. HS for reheating
only
6040
0
Solar
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Type solar control unit"
7A00
0
Parameters for solar control module, type
SM1
C0xx
These parameters will only be displayed if the solar
control module, type SM1, is connected to the heat
pump and
"Type solar control unit"
is set to
"3"
.
For a description of the parameters, see installation
and service instructions for "solar control module, type
SM1".
Commissioning/service reports
Control parameter report
(cont.)
5831412
Appendix