background image

Operation with open flue combustion equipment

Never operate the Vitocal 160-A with extract system together with
open flue combustion equipment (e.g. open fireplaces).
Doors to boiler rooms where the combustion air supply is not inter-
connected with the living space must be airtight and must be kept
shut.

If a Vitocal 160-A is operated together with an open flue heat source
such as the Vitopend or Vitodens, provide an on site fan interlock. This
must switch the fan off as soon as the heat source starts.

Standard ventilation for standard operation

The air flow rate 

´

L

 for basic ventilation of an apartment or utility unit

will be determined by its size, use and occupancy rate. This requires
detailed floor plans and a sectional view of the building, both with
dimensions.
 
The following applies:

´

L

 = n · V

W

´

L

 = 0.5 · h

-1

 · V

W

 
Whereby:

´

L

=

Air flow rate [m

3

/h]

n

=

Air change rate [h

-1

]

V

W

=

Air volume in m

3

, which should be ventilated.

In apartments this includes the heated volume, minus that
of hallways.

For apartments, observe DIN 1946-6. The air flow rates specified by
this standard are listed in the following table.
Air flow rates in the following table are shown subject to the size of the
accommodation and its occupancy rate, without considering window-
less rooms (kitchen, bathroom, WC) in accordance with DIN 1946-6.

Intended
occupancy
rate

Accommoda-
tion size

Basic ventila-
tion

Total ventila-
tion

[occu-
pants]

[m

2

]

 

[m

3

/h]

 

[m

3

/h]

 

up to 2

< 50

 

60

 

60

 

up to 4

< 80

 

90

 

120

 

up to 6

> 80

 

120

 

180

 

Check the calculated air flow rates in the extract air area according to
DIN 1946-6.
Apply the minimum air change rate to DIN 1946, if the calculated basic
ventilation results in a smaller value for the room concerned (see the
following table).

Room

Air change rates for
operational duration >
12 h

Air change rates for any
operational duration

 

[m

3

/h]

[m

3

/h]

Kitchen

40 (200

*4

)  

60 (200

*4

)  

Kitchenette

40  

60  

Bathroom
(also with
WC)

40  

60  

WC

20  

30  

Note
The Vitocal 160-A enables a max. flow rate of 250 m

3

/h with

a pressure of 95 Pa. The flow rate for ventilation mode must be adjus-
ted to the volume of the building and the required air change rate.
We recommend not setting the flow rate below 150 m

3

/h (60% of max.

fan speed).

Extract/expelled air pipework (accessory)

Ventilation elements

Positioning within the room
■ To avoid draughts never position ventilation elements directly next

to seating and sleeping areas.

■ To preheat the outside air during the colder times of the year install

ventilation elements in an area where air convects from radiators.

Sizing
■ Size ventilation elements according to DIN 1946.

Vitovent 300 technical guide

Extract valves

The extract valves can be adjusted to different flow rates up to a stated
max. value (see page 13). The total flow rate of all the extract valves
used must result in 250 m

3

/h.

Extract and expelled air lines

■ Never allow air < 2 °C to enter the extract/expelled air pipework.
■ The connection of cooker hoods to the extract air pipework is not

permitted.

*4

Intermittent ventilation

Design information

 (cont.)

24

VIESMANN

VITOCAL 160-A

6

5822 485 GB

 

Summary of Contents for VITOCAL 160-A

Page 1: ...WWK DHW heat pump for circulating or extract air operation DHW temperatures up to 55 C with heat pump in operation Cylinder capacity 285 litres Air flow rate up to 250 m3 h VITOCAL 160 A Type WWKS DHW...

Page 2: ...ated 15 Flexible pipe compressed 16 Connecting piece 16 Spiral seam tube 16 Bend 90 16 Bend 45 17 Tee 17 Tee reduced 17 Reducer 160 125 17 Reducer 125 100 18 4 DHW cylinder accessories 4 1 Safety equi...

Page 3: ...expansion vessel 30 Sizing the expansion vessel 30 8 Appendix 8 1 Form for designing the sections in the extract expelled air pipework 32 8 2 Form for calculating the total pressure drop in the extra...

Page 4: ...60 A type WWK for circulating mode D Condensate drain G Cold water connection Circulating mode Through the operation of the heat pump the air in the installation room is cooled and the air humidity dr...

Page 5: ...ump and reheating via the electronic immersion heater as in Depending upon the temperature differential between the DHW cylin der and the solar collector the electronic temperature differential con tr...

Page 6: ...incoming sound emission Immission site Measured variable Sound pressure level LP Sound power level LW This describes the entire sound emissions in all directions emanating from the heat pump It is in...

Page 7: ...en lead not only to nui sance in the vicinity but also inside the home For example under unfavourable conditions sound immissions can enter the house via a window In the house itself there is a risk t...

Page 8: ...mode e g switching when you are away a lower fan speed is set for fan stage 2 than for stage 1 Output The Vitocal 160 A is designed so that a DHW volume of approx 1000 l can be heated to 45 C within 2...

Page 9: ...its delivered state The conversion to extract mode is made on site by replacing the cover for circulating mode with the delivered cover for extract mode The removed cover remains with the system user...

Page 10: ...ssure bar 10 Max permiss temperature C 70 Max connectable flat plate collector surface m2 6 Max connectable tube collector surface m2 3 Extract expelled air pipework accessories for extract mode Max p...

Page 11: ...50 100 150 200 250 300 Flow rate in m h Dimensions Type WWK WWKS with cover for circulation mode 700 105 243 609 893 1406 KW E HRS HVS Z KOA WW 660 1785 1846 B ELH VA B Inspection aperture E Drain con...

Page 12: ...ater flow solar thermal system KOA Condensate drain KW Cold water VA Sacrificial anode WW DHW Z DHW circulation Extract expelled air pipework 3 1 Expelled air apertures The expelled air is routed via...

Page 13: ...h removable hood EPP insulation sleeve terminal and lead flashing 600 x 600 mm not shown Pressure drop diagram see page 28 3 2 Ventilation and extract air apertures Arrange the physical geometry of th...

Page 14: ...ram see page 29 Ventilation air filter G3 Part no 7299 301 Fits the ventilation air valve part no 7299 302 Pack containing 10 filters 3 3 Sound insulation and silencer With Vitocal 160 A install a sil...

Page 15: ...ise emis sions and to measuring noise Silencer DN 160 round flexible 1100 DN a Part no 9521 461 Made from flexible pipe Length 1 10 m a 200 mm Attenuation characteristics 125 250 500 1000 2000 8000 Hz...

Page 16: ...mal insulation Connecting piece 100 DN DN 125 Part no 7249 103 DN 160 Part no 9521 437 To join two flexible pipes Spiral seam tube 3000 DN DN 125 Part no 7249 104 DN 160 Part no 9521 428 Length 3 00 m...

Page 17: ...l connections DN 125 or 160 Tee reduced b a b c DN 125 Part no 7299 292 DN 160 Part no 7299 293 Outlet 90 Dimensions and connections Part no a b c 7299 292 DN 125 DN 100 205 mm 7299 293 DN 160 DN 125...

Page 18: ...mann pricelist Design information 6 1 Positioning The Vitocal 160 A should preferably be installed within the air tight and thermally insulated building envelope The Vitocal 160 A for extract mode nee...

Page 19: ...ith high amounts of halogenated hydrocar bons Min room volume 20 m3 Min load bearing capacity of the floor 500 kg Temperature range 2 C to 35 C The appliance must be accessible for maintenance purpose...

Page 20: ...d insulation of the extract expelled air pipework for the Vitocal 160 A in extract expelled mode Provide a silencer see page 15 for the extract and expelled air lines F and G Provide vibration insulat...

Page 21: ...n 60 19 Condensate drainage via water seal 60 19 6 5 Connection to a solar circuit type WWKS By incorporating a solar thermal system the already low costs for DHW heating can be even further reduced W...

Page 22: ...onnection observe DIN 1988 and DIN 4753 Furthermore the following must be observed Connect all pipework with detachable fittings Equip the DHW circulation line with a DHW circulation pump check valve...

Page 23: ...inside and outside of the building Fire safety There is no special requirement for fire safety in detached houses The pipework material for extract mode must be non combustible e g the pipes availabl...

Page 24: ...0 60 60 up to 4 80 90 120 up to 6 80 120 180 Check the calculated air flow rates in the extract air area according to DIN 1946 6 Apply the minimum air change rate to DIN 1946 if the calculated basic v...

Page 25: ...ines To prevent cold air entering lines that draw expelled air outside when the system is not in use in winter install low resistance check valves on site Install ventilation pipes wall outlets and co...

Page 26: ...3 h if the total pressure drop pTotal in the pipework is below 95 Pa see flow rate curve on page 11 The following procedure is advisable for calculating the total pressure drop in the pipework 1 Calcu...

Page 27: ...ent E Extract valves F Silencer optional to reduce transmission of noise through reflec tions telephony effect G Expelled air outlet Flow velocity 0 1 2 3 4 5 6 7 Air flow rate in m h Flow velocity in...

Page 28: ...Outside air inlet grille Air flow rate in m h Pressure drop in Pa 10 0 100 150 200 250 300 350 400 20 30 40 50 60 Expelled air roof outlet 100 Air flow rate in m h Pressure drop in Pa 2 4 6 8 10 0 150...

Page 29: ...al 160 A on site Also install a pump station Solar Divicon in the solar circuit The Vitocal 160 A type WWKS already features the con nections required for connection to the solar circuit The internal...

Page 30: ...ely prevent steam being created during the operating phase collectors in their cold state must be under at least 1 bar pressure The pre charge pressure of the expansion vessel will then be 0 1 x highe...

Page 31: ...t of the solar thermal sys tem z Number of collectors Vk Collector capacity in litres Example System comprising 1 Vitosol 200 type 5DI with 4 2 l capacity Total liquid content of the system VA 22 litr...

Page 32: ...ir pipework Total flow rate max 250 m3 h Project Extract air expelled air area Section no Flow rate Pipework Velocity v Length Number of bends Number of silenc ers Number of tees Pressure drop m3 h m...

Page 33: ...expelled air connector on Vitocal 160 A to the blow off point Pa from the table on page 32 Highest pressure drop section from the extract air valve to the Vitocal 160 A Pa from the table on page 32 wh...

Page 34: ...5 Outside air inlet grille as expelled air roof outlet 160 9562 053 6 Silencer made of flexible tube length 1 1 m 160 9521 461 7 Tee 160 160 160 7190 179 125 125 125 7249 110 8 Tee reduced 160 125 125...

Page 35: ...ning pressure drop 26 DHW boosting 8 DHW circulation line 11 DHW circulation pipe 23 DHW circulation pump 23 DHW connection 11 22 DHW cylinder 8 Capacity 10 max operational pressure 10 DHW temperature...

Page 36: ...ing conditions 10 Operating mode 4 Operating modes 8 Operational cycle 23 Output 8 output data Heat pump 10 Output data electrical 10 Outside air inlet grille 13 28 Outside wall outlet 25 Overflow ape...

Page 37: ...und transmission data 10 Specification 10 Expansion vessel 30 Spiral seam tube 16 Splitting air flow 25 Standard ventilation 24 Standby heat loss 10 Structure borne noise 6 System diagram extract expe...

Page 38: ...38 VIESMANN VITOCAL 160 A...

Page 39: ...VITOCAL 160 A VIESMANN 39 5822 485 GB...

Page 40: ...leached paper Subject to technical modifications Viessmann Limited Hortonwood 30 Telford Shropshire TF1 7YP GB Telephone 44 1952 675000 Fax 44 1952 675040 E mail info uk viessmann com Viessmann Werke...

Reviews: