43
Removing the burner and checking the burner gasket
A
B
C
D
E
F
G
H
K
1.
Switch OFF the main power supply
and the ON/OFF switch at the control
unit.
2.
Close the gas shut-off valve and safe-
guard against reopening.
3.
Unlock control unit
A
and pivot for-
wards.
4.
Remove cover panel
B
.
5.
Pull cables from fan motor
C
, gas
train
D
, ignition unit
E
and ionisa-
tion electrode
F
.
6.
Undo gas supply pipe fitting
G
.
7.
Undo six screws
H
and remove the
burner.
!
Please note
To prevent damage,
never touch the mesh of the
burner gauze assembly.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB