37
Gas type conversion (only for operation with LPG)
1
2
A
1.
Set adjusting screw
A
on the gas
train to "2".
2.
Switch ON/OFF switch "
8
" on.
3.
Select the gas type in coding address
"82":
■ Call up code 2
■ Call up
"General"
(weather-com-
pensated control unit)
or
Group
"1"
(constant temperature
control unit)
■ In coding address "11", select
value "9"
■ In coding address "82", select
value "1" (LPG operation)
■ In code "11", select value
≠
"9".
■ End service functions.
4.
Open the gas shut-off valve.
5.
Affix label "G 31" (included with the
technical documentation) in a clearly
visible position, near the gas train on
the cover panel.
Function sequence and possible faults
Display
Measures
Control unit is-
sues a heat de-
mand
no
Increase set value
and ensure heat is
drawn off
yes
Fan starts
no
After approx. 51 s
fault F9
Check the fan, fan
connecting cables,
power at the fan
and fan control
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5623 520 GB
Service