93
Coding in the delivered condition
Possible change
60:20
During DHW heating, the
boiler water temperature
is max. 20 K higher than
the set DHW tempera-
ture
60:5
to
60:25
The differential between
the boiler water tempera-
ture and the set DHW tem-
perature is adjustable from
5 to 25 K
62:2
Circulation pump with
2 min run-on time after
cylinder heating
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
63:1
Auxiliary function: 1 x daily
63:2
to
63:14
Every 2 days to every 14
days
63:15
2 x daily
65:0
Do not adjust.
67:40
For solar DHW heating:
Set DHW temperature
40 °C. Reheating is sup-
pressed above the selec-
ted set temperature (boil-
er is only connected as
backup if the rise in cylin-
der temperature is too
low).
67:0
to
67:95
Set DHW temperature ad-
justable from 0 to 95 °C
(limited by boiler-specific
parameters)
6F:...
Maximum output for
DHW heating in %, speci-
fied by the boiler coding
card
6F:0
to
6F:100
Max. output for DHW heat-
ing adjustable from min.
output to 100 %
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
71:1
"OFF" during DHW heating
to set value 1
71:2
"ON" during DHW heating
to set value 1
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:1
"OFF" during DHW heating
to set value 2
72:2
"ON" during DHW heating
to set value 2
Code 2
DHW/group "3"
(cont.)
5623 520 GB
Service