67
5.
Set value according to the following
tables with
V
/
v
and confirm with
OK
.
6. If you want to reset all codes to
their delivered condition:
Select
"7"
with
Ú
and confirm with
OK
.
When " " flashes, confirm with
OK
.
Note
This also resets codes at coding level
2.
General/group "1"
Select
"General"
for weather-compensated control units (see page 66).
Select
"1"
for constant temperature control units (see page 66).
Coding
Coding in the delivered condition
Possible change
System design
00:1
System version 1:
One heating circuit with-
out mixer A1 (heating cir-
cuit 1), without DHW
heating
00:2
to
00:10
For system schemes, see
the following table:
Value
address
00: ...
System
version
Description
2
1
One heating circuit without mixer A1 (heating circuit 1), with
DHW heating (code is adjusted automatically)
3
2.3
One heating circuit with mixer M2 (heating circuit 2), without
DHW heating
4
2.3
One heating circuit with mixer (heating circuit 2), with DHW
heating
5
4
One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), without
DHW heating (code is adjusted automatically)
6
4
One heating circuit without mixer A1 (heating circuit 1) and
one heating circuit with mixer M2 (heating circuit 2), with DHW
heating (code is adjusted automatically)
Code 1
Calling up coding level 1
(cont.)
5623 520 GB