Flue terminal position
(cont.)
Vertical flue systems
8
5458 035 GB 08/20
07
Position
Minimum Spacing
C Below eaves
200 mm
D Below a balcony
200 mm
E From vertical drain or soil pipes
150 mm
F From internal and external corners
300 mm
G Above adjacent ground or balcony level/roof
300 mm
H From a surface facing the terminal
600 mm
I Facing terminals
1200 mm
J From opening door/window in carport into dwelling
1200 mm
K Vertically from a terminal on same wall
1500 mm
L Horizontally from a terminal on same wall
300 mm
M Adjacent to opening
300 mm
N Below carport/roof
not recommended
Minimum distance from terminal
Boundary
Walkway
or patio
Car
space
2.5m
2.1m
2.5m
Not under a car port
Avoid access routes and patios
Minimum distance to car
parking space
4
4
7
7