Vitodens 200-W B2HB 45, 57 Installation
31
5680 493 - 05
Waterside Flow
(continued)
Boiler Connections
Model B2HB 57
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output (NG/LPG)
MBH
185
370
555
740
925
1110
1295
1480
t for NG/LPG
20º F (11º C) rise GPM
(L/h)
18.5
(4202)
37.0
(8403)
55.5
(12605)
74.0
(16807)
92.5
(21009)
111.0
(25210)
129.5
(29412)
148.0
(33614)
25º F (14º C) rise GPM
(L/h)
14.8
(3361)
29.6
(6723)
44.4
(10084)
59.2
(13446)
74.0
(16807)
88.8
(20168)
103.6
(23530)
118.4
(26891)
30º F (17º C) rise GPM
(L/h)
12.3
(2801)
24.7
(5602)
37.0
(8403)
49.3
(11205)
61.7
(14006)
74.0
(16807)
86.3
(19608)
98.7
(22409)
35º F (19.5º C) rise GPM
(L/h)
10.6
(2401)
21.1
(4802)
31.7
(7203)
42.3
(9604)
52.9
(12005)
63.4
(14406)
74.0
(16807)
84.6
(19208)
40º F (22º C) rise GPM
(L/h)
9.3
(2101)
18.5
(4202)
27.8
(6303)
37.0
(8403)
46.3
(10504)
55.5
(12605)
64.8
(14706)
74.0
(16807)
Model B2HB 45
1 boiler
2 boilers
3 boilers
4 boilers
5 boilers
6 boilers
7 boilers
8 boilers
Output (NG/LPG)
MBH
149
298
447
596
745
894
1043
1192
t for NG/LPG
20º F (11º C) rise GPM
(L/h)
14.9
(3384)
29.8
(6768)
44.7
(10152)
59.6
(13536)
74.5
(16920)
89.4
(20305)
104.3
(23689)
119.2
(27073)
25º F (14º C) rise GPM
(L/h)
11.9
(2707)
23.8
(5415)
35.8
(8122)
47.7
(10829)
59.6
(13536)
71.5
(16244)
83.4
(18951)
95.4
(21658)
30º F (17º C) rise GPM
(L/h)
9.9
(2256)
19.9
(4512)
29.8
(6768)
39.7
(9024)
49.7
(11280)
59.6
(13536)
69.5
(15792)
79.5
(18048)
35º F (19.5º C) rise GPM
(L/h)
8.5
(1934)
17.0
(3868)
25.5
(5801)
34.1
(7735)
42.6
(9669)
51.1
(11603)
59.6
(13536)
68.1
(15470)
40º F (22º C) rise GPM
(L/h)
7.5
(1692)
14.9
(3384)
22.4
(5076)
29.8
(6768)
37.3
(8460)
44.7
(10152)
52.2
(11844)
59.6
(13536)
Boiler max. flow rate 14.3 GPM (3250 L/h)
Boiler max. flow rate 14.3 GPM (3250 L/h)
Pressure drop (primary circuit) for
Vitodens 200-W, B2HB 45 - 57
For sizing an on-site circulation system.