Vitodens 200-W B2HB 45, 57 Installation
41
5680 493 - 05
Boiler Connections
System Layout 9
Multiple (up to eight) Vitodens 200-W, models B2HB 45 to 57 with...
- multiple heating circuits with mixing valves
- low-loss header
When designing a multiple Vitodens system as shown
above, please reference applicable multiple Vitodens
technical documentation, and contact your local Viessmann
Sales Representative for further assistance.
T
his installation example depicts a possible piping layout
for multiple Vitodens 200-W, B2HB boilers equipped with
Viessmann System Technology. Please note that this
example is based on a simplified conceptual drawing only!
Piping and necessary componentry must be field verified.
A low water cut-off (LWCO) must be installed where
required by local codes.
Proper installation and functionality in the field is the
responsibility of the heating contractor.
WARNING
If a DHW storage tank other than a Viessmann
Vitocell 100 or 300 tank is used, the installer must
verify proper operation of the Viessmann DHW tank
temperature sensor with the original manufacturer
of the tank. Viessmann strongly recommends the
installation of a temperature tempering valve in the
DHW supply line.
Legend
A
Vitodens
boiler
B
Vitotronic
300K
C
Low-loss header/common supply temperature sensor
D
Low-loss
header
E
DHW storage tank
F
High temperature heating circuit
G
Low temperature heating circuit