Vitodens 200-W B2HB 45, 57 Installation
5680 493 - 05
14
Wall Mounting
(continued)
Boiler Connections
Installation on wood studs
Install mounting bracket on wood studs as per illustration.
Drill
3
/
16
” pilot holes to insert mounting bolts. Ensure that
holes are located in the center of each wood stud. Secure
with bolts to wooden studs as shown.
Installation on metal studs
install mounting bracket on metal studs as per illustration.
Drill
f
” pilot holes to insert anchors. Ensure that holes are
located in the center of each metal stud. Use appropriate
fasteners to mount to metal studs (not supplied). Secure
with bolts to metal studs as shown. Ensure the mounting
bracket is level.
Boiler mounting bracket
Install the boiler mounting bracket to the wall studs.
Ensure the mounting bracket is level.
To mount on wood or metal studs a cross bar or frame
may be required as reinforcement. The wall and studs
must be capable of supporting a minimum of 210 lb.
(95 kg).
For construction materials, use fixings that are suitable
for 210 lb (95 kg) loads.