41
6167 818 - 10
Vitodens 100-W, B1HE/B1KE Combi Installation/Service
Commissioning
Commissioning the System with the Commissioning Assistant
(continued)
Commissioning assistant sequence Explanations and references
Operating mode
Weather-compensated
Constant operation
Outside temperature sensor connected.
With outside temperature value.
System scheme
DHW
Not installed
Cylinder with one sensor with
/without DHW recirculation
pump
DHW comfort function
Tank with temperature switch
(Aquastat) with/without DHW
recirculation pump
Settings for DHW heating according to the system components
System without DHW heating
System with DHW tank with 1 tank temperature sensor
Only for B1KE series boilers (not adjustable)
No demand from Aquastat = no frost protection
Demand from Aquastat = demand for target value
Low loss header/buffer tank
Not installed
Low loss header, heating only
DHW heating upstream of
low loss header
DHW heating downstream
of low loss header
Settings for the consumer circuits according to the system components.
Note:
All system schemes with low loss header without temperature sensor
for low loss header.
There is no low loss header or heating water buffer tank in the system.
System with low loss header, without DHW heating.
DHW heating with e.g. separate DHW tank connected upstream of the low
loss header.
DHW heating with e.g. separate DHW tank connected downstream of the
low loss header.
Plug 96
Heat demand (“call for heat”)
If a contact has been connected to plug 96.
Maintenance
Interval in burner hours run until
next maintenance
Interval adjustable in steps of 100 h.
Interval until next maintenance
Interval adjustable to 3, 6, 12, 18 or 24 months.
The boiler control carries out a restart.
Affix a further credentials label here, so it can be found
for subsequent use:
Affix a label in the operating instructions.
Calling up the commissioning assistant at a later point
If you need to continue commissioning later, the
commissioning assistant can be reactivated at any time.
Tap the following buttons:
1.
and OK simultaneously for approx. 4 sec, then release.
2. Use
to select “Basic settings”.
3. OK
4. Use
to select “Commissioning assistant”.
5. OK
Switching WiFi ON/OFF
The boiler is equipped with an integrated WiFi
communication module with extended rating plate.
The internal communication module supports
commissioning of the boiler with the “Vitoguide mobile
app”, connectivity with the “ViCare app”, and connection
to the “Vitoguide” digital service centre.
The access details required for establishing a connection
are recorded in the form of an access code with
“WiFi symbol”. Three copies of this code are located
on the rear of the programming unit.
Before installing the programming unit, remove the access
code labels from the rear. For commissioning, affix one
label to the front of the boiler.
Switch on the WiFi connection and establish a connection
to the router; see also page 29.
Activating the internet connection:
Operating instructions
Place WiFi label here