171
Type BW in conjunction with "conversion kit for water/wa-
ter heat pump"
351.A07
Output data
to EN 14511 (W10/W35, 5 K spread)
Rated heating output
kW
10.22
Cooling capacity
kW
8.59
Power consumption
kW
1.75
Coefficient of performance ε (COP)
5.83
Brine
(primary circuit)
Capacity
l
4.0
Min. flow rate (spread 4 K)
l/h
2000
Pressure drop (at min. flow rate)
mbar
75
kPa
7.5
Max. flow temperature
°C
25
Min. flow temperature
°C
7.5
Heating water
(secondary circuit)
Capacity
l
3.4
Min. flow rate (spread 10 K)
l/h
900
Pressure drop (at min. flow rate)
mbar
25
kPa
2.5
Max. flow temperature
°C
72
Electrical values, heat pump
Rated voltage, compressor
3/N/PE
400 V/50 Hz
Rated current, compressor
A
8.2
Starting current, compressor (with starting current lim-
iter)
A
21.0
Starting current, compressor with stalled armature
A
51.5
Compressor fuse
A
1 x B16A 3-pole
Electrical values, control unit
(only for type BW)
Rated voltage
1/N/PE
230 V/50 Hz
Fuse protection
B16A
Fuses
2 x 6.3 A H/250 V
Max. power consumption
W
1000
Power consumption in operation
W
10
Specification
Specification for water/water heat pumps
5609 667 GB
Service