167
Type BW/BWS
351.A07
Output data
to EN 14511 (B0/W35, 5 K spread)
Rated heating output
kW
7.35
Cooling capacity
kW
5.83
Power consumption
kW
1.63
Coefficient of performance ε (COP)
4.50
Output data
to EN 14511 (B0/W35, 10 K spread)
Rated heating output
kW
7.55
Cooling capacity
kW
6.05
Power consumption
kW
1.60
Coefficient of performance ε (COP)
4.70
Brine
(primary circuit)
Capacity
l
4.0
Min. flow rate (spread 5 K)
l/h
1100
Pressure drop (at min. flow rate)
mbar
40
kPa
4
Max. flow temperature
°C
25
Min. flow temperature
°C
–10
Heating water
(secondary circuit)
Capacity
l
3.4
Min. flow rate (spread 10 K)
l/h
650
Pressure drop (at min. flow rate)
mbar
14
kPa
1.4
Max. flow temperature
°C
72
Electrical values, heat pump
Rated voltage, compressor
3/N/PE
400 V/50 Hz
Rated current, compressor
A
8.2
Starting current, compressor (with starting current lim-
iter)
A
21.0
Starting current, compressor with stalled armature
A
51.5
Compressor fuse
A
1 x B16A 3-pole
Electrical values, control unit
(only for type BW)
Rated voltage
1/N/PE
230 V/50 Hz
Fuse protection
B16A
Fuses
2 x 6.3 A H/250 V
Max. power consumption
W
1000
Power consumption in operation
W
10
Specification
Specification for brine/water heat pumps
5609 667 GB
Service