51
Clamps
Function
Explanation
630XD2
1: External potential
2: Signal (digital)
Common alarm prio. 2 heat pump
Floating N/O contact:
Closed: Standard mode
Open:
Fault
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
630XD3
1: External potential
2: Signal (digital)
Refrigerant alarm
Floating N/O contact:
Closed: Standard mode
Open:
Fault
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
630XD4
1: External potential
2: Signal (digital)
Operating message, heat pump
Floating N/O contact:
Closed: Operation
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
630XD5
1: External potential
2: Signal (digital)
Demand, immersion heater, heat-
ing water buffer cylinder
Floating N/O contact:
Closed: No demand
Open:
Demand
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
630XD6
1: External potential
2: Signal (digital)
Start command, external heat
generator
Floating N/O contact:
Closed: Demand
Open:
No demand
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
630XD7
1: External potential
2: Signal (digital)
Demand, immersion heater in
DHW cylinder
Floating N/O contact:
Closed: No demand
Open:
Demand
Connection values:
■
Max. voltage: 250 V~
■
Max. switching current: 5 A (AC1)
800KF0
X102: LAN1
Modbus TCP/BACnet IP
ADS
DHCP is active
Connection with RJ45 plug directly to
socket of panel PC 800KF0
800KF6
2: EtherCAT OUT
EtherCAT bus connection
From: Heat pump
To: Hydraulic module defrost box
Connection with RJ45 plug directly to
socket of bus coupler EK1100
Power supply
Isolators for non-earthed conductors
■
The integral ON/OFF switch must simultaneously
isolate all non-earthed conductors from the mains
with a minimum contact separation of 3 mm.
■
Install an isolator in the power cable to provide
omnipolar separation from the mains for all active
conductors, corresponding to overvoltage category
III (3 mm) for full isolation. This isolator must be fitted
in the permanent electrical installation in line with
installation requirements, e.g. mains isolator or
upstream circuit breaker.
Installation procedure, heat pump
Electrical connections
(cont.)
5837251
Installation