Information regarding transport with forklift truck
■
Select a fork length appropriate for the total appli-
ance length; see "Specification".
■
Always centre the forklift truck forks on the centre of
gravity.
The centre of gravity is located on the left (opposite
the hydraulic connections).
■
Use required edge protection (e.g. 2 or 3 layers of
corrugated cardboard).
Hydraulic module siting requirements
The installation room must be dry and safe from the
risk of frost (> 3 °C).
Moving components in the hydraulic module (e.g. cir-
culation pumps) transmit low level airborne and struc-
ture-borne noise.
Recommendation: Never install the appliance in living
spaces or directly next to, below or above quiet rooms/
bedrooms.
The requirements for hydraulic connections and sound
insulation correspond to the requirements for heat
pumps. See chapter "Siting requirements for the heat
pump".
Observe minimum clearances for installation and
maintenance.
Minimum clearances to the wall or heat pump
950
1800
600
850
850
600
3350
2300
Fig. 12
A
Hydraulic module
B
Service side
C
Connection side
D
Clearance (according to DIN 18101):
≥
944 mm
Pressure points of the hydraulic module feet
770
1800
850
80
80
860
860
Fig. 13
Preparing for installation
Transport and siting requirements: Hydraulic…