Item
Default
Description
Periodic run
No
Enable - No / Yes
Run interval
Skip run if has been running for
Run interval start date
Start time
Run duration (hh:mm)
Run until battery is fully charged
Generator start/stop -> Settings
Minimum run time
0
The minimum number of minutes the generator will run for any
time that it is started, even after stop conditions.
Detect generator at AC
input
No
No / Yes - An alarm will be triggered when no power from the
generator is detected at the inverter AC input. Make sure that the
correct AC input is set to generator on the system setup page.
Quiet hours
0
Quiet hours will prevent normal generator run conditions from
starting the generator. It is possible for some settings to specify
override values to the quiet hours ( an extremely low battery
voltage trigger to prevent a system shutdown for example)
Reset daily run time
counters
An option to reset generator run time counters, for example if
these are used for service, or if the generator is replaced or
majorly repaired.
Generator total run time
(hours)
The total time the generator has been running since the counter
was reset.
Tank pump
Configure automatic starting and stopping of pump based on tank level(sender) information.
Pump auto start/stop with Color
Pump state
Displays if the pump is running or not
Mode
Auto
Options are Auto, On and Off. This is the manual override to the
start and stop level triggers when a tank sensor is connected.
Tank Sensor
Automatic
Select the tank sensor that is used for the tank pump trigger. 'No
tank sensor' will be displayed if no tank sensor is connected or
detected,
Start level
50%
The trigger point of the tank level to start the tank pump (close
the relay).
Stop level
80%
The trigger point of the tank level to stop the tank pump (open
the relay).
Relay
Function
Alarm relay
Select the relay function. Possible functions are 'Alarm relay',
'Generator start/stop', 'Tank pump' and 'None' (disabled).
Polarity
Normally open
Select the polarity of the relay on the back of the CCGX.
'Normally open' or 'Normally closed'. (Note that setting it to
normally closed increases the CCGX power draw.)
Services
ModbusTCP
Off
This setting enables the ModbusTCP service. More information
about
https://www.victronenergy.com/upload/documents/
Whitepaper-Data-communication-with-Victron-Energy-
products_EN.pdf
MQTT on LAN (SSL)
On
Enables MQTT on LAN - More information on MQTT is available
on
MQTT on LAN (Plaintext)
Off
This setting is required to be enabled when connecting an
Marine MFD
VE.Can port
VE.Can
CAN-bus profile (Disabled, VE.Can & Lynx Ion BMS 250 kbit/s,
VE.Can & Can-bus BMS 250 kbit/s, CAN-bus BMS 500 kbit/s,
Oceanvolt 250 kbit/s), Send data to VE.Can, Unique device
number for VE.Can, Check unique numbers
Color Control GX Manual
Page 26
Configuration