03.2021
INSTRUCTION MANUAL
for installation and operation of pellet stove
VITTORIA 8
15
When the time is over, the device transfers to Fuel Mode. In this mode there is a countdown
as well. The screw conveyor gets active and starts fuelling on impulses within the following
period
–
2 seconds fuels/ 3 seconds rests.
The ignition (switch) is also active now.
In this mode one can regulate the operation time. Regulating it defines what quantity of
pellets is released. Changing it is possible in the Ignition/ Initial Fuel Menu.
When the time is over, the device transfers to Ignition Mode. In this mode the ignition
switch is still active, the screw conveyor can be set in time for fuel and rest, and will keep on
operating.
Setting these parameters can be done in Ignition/ Fuel Screw Conveyor/ Screw Conveyor
Menu.
This mode is a transitory one, to transfer to the next mode the exhaust gas sensor needs to
detect an increase in the temperature above the one, which has been pre-set, in the Ignition/
Temperature On Menu!
The increase must last at least 10 seconds and be with at least 6 degree more than the
temperature at which the Control Unit has entered the Ignition Mode!
If this requirement has not been met and the pre-set time is over, the device would make a
second attempt to fuel; its time has been pre-set in the Ignition/ Second Fuel Menu.
If the requirement is met, the device will transfer to Set Fire Mode.
In this mode, the idea is to set the pellets on fire and get stable flame.
The settings of this mode can be found in the Set Fire Menu. When the time of the Set Fire
Mode is over, the device will transfer to the Modulation Mode,
after transfer Temperature
OFF. The first one to start is P5, followed by P4 and in the end P1.
Switching among these is based on the temperature, pre-set as room temperature.
If the room temperature is set to 3
0°С.
- in the Modulation 5 Menu / the Thermal Difference one should set is 4
°С
- in the Modulation 4 Menu / the Thermal Difference one should set is
3°С
- in the Modulation 3 Menu / the Thermal Difference one should set is
2°С
- in the Modulation 2 Menu / the Thermal Difference one should set is
1°С
- in the Modulation 1 Menu / the Thermal Difference one should set is
0°С
Under the parameters set as above, the process will go like this:
On reaching 2
6°С, which is 4°С below the
pre-set, Modulation 4 will launch.
On reaching 27
°С, which is
3
°С below the
pre-set, Modulation 3 will launch.
On reaching 28
°С, which is
2
°С below the
pre-set, Modulation 2 will launch.
On reaching 29
°С, which is
1
°С below the
pre-set, Modulation 1 will launch.
On reaching the pre-set temperature, the device will transfer to Stop Mode.
In the Stop Mode, Clean on Extinct Fire will launch.
On passing the time for Clean on Stop, the device would transfer to Green Eco
Mode.
ECO mode
is activated after the set room temperature is exceeded by 1
0
C.
When the set time for cleaning during stopping procedure runs out, the control
unit shifts to ECO mode. In ECO mode two very important conditions have to be
completed:
•
first is to run out the set time of 600 seconds;
•
after that, check-up is made is the room temperature below the set with
2
°С
.
When these two conditions are completed the control unit shifts to start up
procedure.
The Modulations can be changed through pressing the mode display field on which modulation the device is to
operate under!
Meaning, if we are on Modulation 5 on pressing the selection field, it will redirect to Modulation Change Menu.
It is important to note that this change is permanent. It is saved and on restarting the control unit and reaching
the modulations, if Modulation 2 is pre-set, then the device would transfer to it directly!
Summary of Contents for VITTORIA 8
Page 1: ...INSTRUCTION MANUAL for installation and operation of air pellet stove VITTORIA 8...
Page 4: ...Victoria 05 Ltd 4 3 Technical data and dimensions Drawing 1...
Page 20: ...Victoria 05 Ltd 20...
Page 21: ...03 2021 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 21...
Page 22: ...Victoria 05 Ltd 22...