VD530 Series Inverter User Manual Function Parameter Table
- 63 -
F8-13
Quick Start Over
current
Suppression
Gain
0~1000
100
○
F8-14
Short-circuit to
Ground Upon
Power-on
0: Invalid
1: Valid
1
○
F8-15
Input Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
○
F8-16
Output Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
◎
F8-17
Offload
Protection
Selection
0: Invalid
1: Valid
0
○
F8-18
Offload
Detection Level
0.0~100.0%
10.0%
○
F8-19
Offload
Detection Time
0.0s~60.0s
1.0s
○
F8-20
Overspeed
Detection Value
0.0%~50.0% (max frequency)
20.0%
○
F8-21
Overspeed
Detection Time
0.0: No detection
0.1s~60.0s
0.0s
○
F8-22
Large Speed
Deviation
Detection Value
0.0%~50.0% (max frequency)
20.0%
○
F8-23
Large Speed
Deviation
Detection Time
0.0: No detection
0.1s~60.0s
0.0s
○
F8-24
Action Selection
Upon
Instantaneous
Power Failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0
○
F8-25
Voltage Restore
Judgment Value
Upon
Instantaneous
Power Failure
F0-10~100.0%
90.0%
○
F8-26
Voltage Restore
Judgment Time
Upon
Instantaneous
Power Failure
0.00s~100.00s
0.50s
○