VD530 Series Inverter User Manual Parameter Description
- 161 -
with according to the selected fault processing method.
FA-28
PID Feedback Lost
Detection Starting
Frequency
0.00Hz~max frequency
10.00Hz
○
FA-29
PID Stop Operation
0: No operation when stop
1: Operation when stop
0
○
Used to select the PID in stop condition, PID whether to continue operations. General application in
the case of PID should stop operation under the stop condition.
FA-30
The Lower Limit Value of
Feedback when PID
Action
0.0%: No limit
0.1%~100.0%
0.0.%
○
When the PID feedback value is less than the lower limit, the PID regulation does not act, which is
mainly used to reduce PID regulation and maintain the stability of the system.
Fb Enhance Function Group
Fb-00
Jog Running Frequency
0.00Hz~max frequency
2.00Hz
○
Fb-01
Jog Acceleration Time
0.0s~6500.0s
20.0s
○
Fb-02
Jog Deceleration Time
0.0s~6500.0s
20.0s
○
Definition the given frequency and acceleration/deceleration time of frequency converter in jog.
When jog running, the start mode is fixed to the direct start mode (F1-00=0) and the stop mode is
fixed to the deceleration stop (F1-08=0).
Fb-03
Acceleration Time 2
0.0s~6500.0s
Model dependent
○
Fb-04
Deceleration Time 2
0.0s~6500.0s
Model dependent
○
Fb-05
Acceleration Time 3
0.0s~6500.0s
Model dependent
○
Fb-06
Deceleration Time 3
0.0s~6500.0s
Model dependent
○
Fb-07
Acceleration Time 4
0.0s~6500.0s
Model dependent
○
Fb-08
Deceleration Time 4
0.0s~6500.0s
Model dependent
○
VD530 provide four groups of acceleration/deceleration time, respectively F0-18/F0-19 and the above
three groups of acceleration/deceleration time.
The definition of four groups of acceleration/deceleration time are exactly the same, please reference
F0-18 and F0-19 related instructions.
Through the different combination of the multi-function digital inputs terminal DI, it can be switched to
select 4 groups of acceleration/deceleration time.
Schedule 1 is the terminal functional specifications of acceleration/deceleration time selection.
Terminal 2 Terminal 1
Acceleration/deceleration time selection
Corresponding Parameter
OFF
OFF
Acceleration time 1
F0-18, F0-19
OFF
ON
Acceleration time 2
Fb-03, Fb-04
ON
OFF
Acceleration time 3
Fb-05, Fb-06
ON
ON
Acceleration time 4
Fb-07, Fb-08