VD530 Series Inverter User Manual Function Parameter Table
- 49 -
F3-01
Speed Loop
Integral Time 1
0.01s~10.00s
0.50s
○
F3-02
Switch
Frequency 1
0.00~F3-05
5.00Hz
○
F3-03
Speed Loop
Proportional
Gain 2
1~100
20
○
F3-04
Speed Loop
Integral Time 2
0.01s~10.00s
1.00s
○
F3-05
Switch
Frequency 2
F3-02~max frequency
10.00Hz
○
F3-06
Vector Control
Slip Gain
20%~200%
100%
○
F3-07
Speed Loop
Filter Time
Constant
0.000s~0.100s
0.000s
○
F3-09
Speed Control
Mode Torque
Upper Limit
Source
0: Encode F3-10 setting
1: AI1
2: AI2
3: AI (expansion card)
4: PULSE setting
5: Communication setting
6: MIN (AI, AI2)
7: MAX (AI1, AI2)
The full scale of options 1~7
corresponding to the F3-10
0
○
F3-10
Digital Setting
for Speed
Control Mode
Torque Upper
Limit
0%~200.0%
150.0%
○
F3-13
Excitation
Adjustment
Proportional
Gain
0~60000
2000
○
F3.14
Excitation
Adjustment
Integral Gain
0 ~60000
1300
○
F3-15
Torque
Adjustment
Proportional
Gain
0~60000
2000
○
F3-16
Torque
Adjustment
Integral Gain
0~60000
1300
○