Function Parameter Table VD530 Series Inverter User Manual
- 62 -
F8 Protection Parameters
Function
Code
Parameter
Name
Setting Range
Factory
Default
Value
Property
F8-00
Motor 1
Overload
Protection
Selection
0: Disabled
1 : Enabled
1
○
F8-01
Motor 1
Overload
Protection Gain
0.20~10.00
1.00
○
F8-02
Motor 1
Overload
Warning
Coefficient
50%~100%
80%
○
F8-03
Motor 2
Overload
Protection
Selection
0 : Disabled
1 : Enabled
0
○
F8-04
Motor 1
Overload
Protection Gain
0.20~10.00
1.00
○
F8-05
Motor 1
Overload
Pre-alarm
Coefficient
50%~100%
80%
○
F8-06
Overvoltage/ove
r current Stall
Mode Selection
0: Mode 0
1: Mode 1
≤11kW: 1
◎
>11kW: 0
F8-07
Overvoltage Stall
Proportion Gain
0: Disabled
1~100
10
○
F8-08
Overvoltage Stall
Integral Gain
0~100
5
○
F8-09
Overvoltage Stall
Protection
voltage
100.0VDC~800.0VDC
380VAC: 700.0VDC
○
220VAC: 370.0VDC
F8-10
Over current
Stall Proportion
Gain
0: Disabled
1~1000
20
○
F8-11
Over current
Stall Integral
Gain
0~1000
20
○
F8-12
Over current
Stall Protection
Current
100%~200%
160%
○