VD530 Series Inverter User Manual Function Parameter Table
- 51 -
F4-03
Manual Torque
Boost Cutoff
Frequency
0.00Hz~max frequency
50.00Hz
◎
F4-04
MS VF
Frequency Point
1
0.00Hz~F4-05
0.00Hz
◎
F4-05
MS VF Voltage
Point 1
0.0%~100.0%
0.0%
◎
F4-06
MS VF
Frequency Point
2
F4-04~F4-07
0.00Hz
◎
F4-07
MS VF Voltage
Point 2
0.0%~100.0%
0.0%
◎
F4-08
MS VF
Frequency Point
3
F4-05~Rated motor frequency (F2-04)
0.00Hz
◎
F4-09
MS VF Voltage
Point 3
0.0%~100.0%
0.0%
◎
F4-10
VF Slip
Compensation
Gain
0.0%~200.0%
20.0%
◎
F4-12
VF Oscillation
Suppression
Gain
0~100
Model
dependen
t
○
F4-14
The Separation
of VF Voltage
Source
0: Digital setting (F4-15)
1: AI1
2: AI2
3: AI3 (expansion card)
4: PULSE setting
5: MS instruction
6: Simple PLC
7: PID
8: Communication given
Remark: 100% corresponding rated
motor voltage
0
○
F4-15
VF Separation
Voltage Digital
Setting
0V~rated motor voltage
0V
○
F4-16
VF Separation
Voltage Rise
Time
0.0s~1000.0s
Remark: Indication the time that 0V rise
to rated motor voltage
5.0s
○
F4-17
VF Separation
Voltage Fall
Time
0.0s~1000.0s
Remark: Indication the time that rated
motor voltage drop to 0V
5.0s
○