69
Viconics Technologies Inc.
www.viconics.com
028-0444-06
November 2018
1 2 3 4 5 6
13 14 15 16 17 18
7 8 9 10 11 12
19 20 21 22 23 24
1 2 3 4 5 6
13
7 9 1
VT8350
BO2 - F
an L
BO3 - F
an M
BO4 - F
an H
R
C (24 V
ac)
C (Common)
RH
BO8 - A
ux Hea
t
UO10 - E
CM
UO11
- Analog Hea
t
UO12
- Analog Cool
B
A
Cnet +
B
A
Cnet -
B
A
Cnet REF
UI 16
UI 17
Common
UI 19
UI 20 - RS
Common
UI22 - SS
Modulating C ECM Fan
(-)
(+)
ECM Fan
HEATING VALVE
0-10 v 24 v Com.
COOLING VALVE
0-10 v 24 v Com.
COMM ON
24 VAC
FAN START
FCU Low-voltage
TERMINAL BLOCK
(OPTIONAL)
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating. The changeover sensor sends supply air temperature to controller.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature. Heating valve closes. Dehumidification enabled.
On Call for Heat
Heating valve opens to maintain room temperature. Cooling valve closes. Dehumidification disabled.
On Demand for Dehumidification
Dehumidification is achieved via cooling coil using heating coil for reheat if necessary.
Dehumidification only allowed in COOL mode, or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Reheat disabled if cooling demand reaches 100%.
Summary of Contents for VT8300 Series
Page 8: ...VTR83 3 Speed ...
Page 27: ...VTR83 ECM ...
Page 44: ...VT83 3 Speed ...
Page 63: ...VT83 ECM ...
Page 83: ...VT83 MIX VOLTAGE ...