Options
•
Wireless adapter modules are available. (see Appendix B for network wiring).
•
Models available with factory installed PIR sensor.
•
Remote wall mount or duct sensor ready.
•
Can be configured for 2-pipe systems with changeover.
•
Binary inputs can be configured to control occupancy via door or window contact, remote night setback, or provide alarms for
service or filter monitoring.
•
Universal input can be configured for changeover sensor.
ECM Fan Operation
System Off
UO12 = 0Vdc and brown wire (fan start) is not energized
System On: (Fan modes)
•
Low: UO12 = 2.2 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
•
Med: UO12 = 6.0 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
•
High: UO12 = 8.6 Vdc (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.
•
Auto: When there is no demand, UO12 = 0 Vdc and (optional) brown wire “fan start”is “off”. On demand, system will modulate
from “low” to “high” voltages (adjustable from configuration menu) and (optional) brown wire “fan start” is energized.