13
Viconics Technologies Inc.
www.viconics.com
028-0444-06
November 2018
Tx/Rx
7 Vdc
Com
RUI 1
SCom
RBI 2
SS
RS
Heat -
Heat +
1
2
3
4
5
6
7
8
9
10
SOLIDSTATE
RELAY
(4-32Vdc)
(-)
(+)
VC3404E5000
VTR8350
BA
Cnet+
BA
Cnet
-
BA
Cnet REF
UI 16 - BI1
UI 17 - BI2
SC
om
Tx / Rx
7 VDC
Co
m
WHT
BLK
RED
BLU
GRN
YEL
ORG
NOTE: See Appendix B for VC3400
wiring to fan coil
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those defined by occupied cooling and heating.
Stand-by Mode (only available when PIR motion detector sensor is used)
Setpoints revert to those defined by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those defined by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime” parameter.
On Call for Cool
Cooling valve opens to maintain room temperature.
On Call for Heat
Electric heat operates to maintain room temperature. Cooling valve closes and dehumidification is disabled.
On a Demand for Dehumidification
Dehumidification achieved via cooling coil using reheat if necessary.
Dehumidification only allowed in COOL mode or if cooling is enabled in AUTO mode.
Dehumidification disabled if room temperature falls below low ambient lockout temperature, which is cooling setpoint minus
configuration defined deadband value.
Summary of Contents for VT8300 Series
Page 8: ...VTR83 3 Speed ...
Page 27: ...VTR83 ECM ...
Page 44: ...VT83 3 Speed ...
Page 63: ...VT83 ECM ...
Page 83: ...VT83 MIX VOLTAGE ...