Viconics Technologies Inc.
www.viconics.com
028-0444-06
November 2018
10
Configuration
Parameter Name
Configuration Settings
Fan control
3 speed
Fan Menu
L-M-H-A
Fan cont. heat.
On
BI1
Motion NO or Motion NC (remote PIR sensor only)
BI2
Door Dry
Pulsed heating
Off
Pipe no.
4
Seq. operation
Ht - Cl
VTR83X0A5X00B WITH VC3500E5000 RELAY AND VCM8000V5000P ZIGBEE PRO MODULE: HEATING/
COOLING 4-PIPE FAN COIL UNIT WITH 3-SPEED FAN AND 2-POSITION VALVES
* Wired remote sensor cannot be used at the same time as wireless remote sensor(s).
VC3500E5000
2 POSITION
COOLING VALVE
Cooling Coil
2 POSITION
HEATING VALVE
Heating Coil
Airflow Direction
3 Speed Fan
VTR83X0
Onboard
PIR Sensor
AND / OR
OR*
Wired Remote
PIR Sensor
Wireless Remote
PIR Sensor