49
16. Defects and their elimination (rectification)
The defects can only be eliminated by a trained contractual service organization which is also obliged to
enter the repair in the guarantee certificate.
The defects market with symbol “
∗∗∗∗
„ can be eliminated by the user himself.
If the safety thermostat or the combustion products return flow fuse get repeatedly blocked it is also
necessary to call a contractual service worker.
DEFECT
REASON
ELIMINATION
1.
After having switched on the boiler
the control lamp on the main
switch does not light up
No voltage on the boiler inlet
Check the voltage in the socket
Faulty control lamp
Faulty fuse
Exchange the switch
Exchange the fuse
2.
Boiler cannot be started – the
ignition electrode for pilot burner
ignition does not sparkle.
Faulty automatics
Exchange the automatics
Interrupted inlet to the ignition
Check the perfect connection between
the electrode and the HV output to the
automatics
Faulty electrode
Exchange the electrode
3.
Boiler
cannot
be
started
–
sparkling runs in the automatics
spark gap (discharger) (audible
sparkling sound in automatics)
(only the natural gas)
Wrong spark gap(discharger)
setting
Adjust according to Fig. no. 4a, 4b
Wrong conductors connection to
electrodes or a faulty electrode
Check the electrodes condition and
connection
of
ignition
and
earth
conductor
4.
Boiler doesn’t ignite - the ignition
electrode is sparkling– Hon. Ts´=
55 s; SIT Ts´= 60 s (on the burner
automatics the „ALARM“ control
lamp lights up in the automatics
with signalisation
Boiler gas supply is interrupted
Check the gas pressure in gas
connection
* Check the appliance gas closure
opening
Gas piping air lock
Bleed the piping
Gas valve does not open
Valve exchange
5.
Boiler lit but is out immediately
(on the burner automatics the
„ALARM“
signal
lamp
of
automatics with signalisation lights
up)
Wrong connection between the
zero and phase conductors
Check and exchange the connection
terminal U – phase conductor
terminal N – zero conductor
Wrong diameters of gas nozzles in
burner
Check whether the nozzles diameter in
the main burner corresponds to the
values in tables no. 2 – 5.
Impassable
filter
of
course
impurities on gas valve inlet
Clean the gas valve filter by blowing out
(in
case
of
fine
impurities
the
dimensions of which are the same as
the filter mesh diameter the whole gas
valve must be exchanged)
6.
Boiler cannot be ignited– the
safety thermostat switched off (on
the control panel in the network
module the exceeded temperature
signal lamp lights up)
Faulty boiler thermostat
Exchange the boiler thermostat
* Unblock the thermostat in network
module - TB
Insufficient water circulation
(the pump doe not work)
* Switch over the revolutions
Check the pump operation (release the
rotor)
Exchange the pump
filter clogged before the pump
* Clean the filter
Lack of water in the system
* Check the water pressure in the system
and possible water refilling
Check the pressure in the expansion
tank (if a closed heating system is used)
* Check the three-way valve
(if the HWS heating is connected)
7.
Boiler does not switch over
between the rated and reduced
output at the temperature set on
the outdoor thermostat and the
reduced output switch is in
position “I” (only at the boiler
equipped with double stage gas
valve)
Faulty outdoor thermostat
If need be exchange outdoor thermostat
Interrupted connection between the
outdoor thermostat and the boiler
Check the connection
Faulty High-Low coil
Exchange the coil
Summary of Contents for GARDE G 42 ECO
Page 52: ...52...
Page 56: ...56...
Page 58: ...58...
Page 59: ...59...
Page 60: ...60 Date of revision 16 2013 GB...