22
Time program 3/HC3
Parameter
Function
Factory settings
Min.
Max.
Units
540
Preset
Mo-Su
00:00
24:00
hh:mm
541
Mo-Su : 1. Phase ON
6:00
00:00
24:00
hh:mm
542
Mo-Su : 1. Phase OFF
22:00
00:00
24:00
hh:mm
543
Mo-Su : 2. Phase ON
24:00
00:00
24:00
hh:mm
544
Mo-Su : 2. Phase OFF
24:00
00:00
24:00
hh:mm
545
Mo-Su : 3. Phase ON
24:00
00:00
24:00
hh:mm
546
Mo-Su : 3. Phase OFF
24:00
00:00
24:00
hh:mm
556
Standard values
NO
Time program 4/HW
Parameter
Function
Factory settings
Min.
Max.
Units
560
Preset
Mo-Su
00:00
24:00
hh:mm
561
Mo-Su : 1. Phase ON
6:00
00:00
24:00
hh:mm
562
Mo-Su : 1. Phase OFF
22:00
00:00
24:00
hh:mm
563
Mo-Su : 2. Phase ON
24:00
00:00
24:00
hh:mm
564
Mo-Su : 2. Phase OFF
24:00
00:00
24:00
hh:mm
565
Mo-Su : 3. Phase ON
24:00
00:00
24:00
hh:mm
566
Mo-Su : 3. Phase OFF
24:00
00:00
24:00
hh:mm
576
Standard values
NO
Time program 5
Parameter
Function
Factory settings
Min.
Max.
Units
600
Preset
Mo-Su
00:00
24:00
hh:mm
601
Mo-Su : 1. Phase ON
6:00
00:00
24:00
hh:mm
602
Mo-Su : 1. Phase OFF
22:00
00:00
24:00
hh:mm
603
Mo-Su : 2. Phase ON
24:00
00:00
24:00
hh:mm
604
Mo-Su : 2. Phase OFF
24:00
00:00
24:00
hh:mm
605
Mo-Su : 3. Phase ON
24:00
00:00
24:00
hh:mm
606
Mo-Su : 3. Phase OFF
24:00
00:00
24:00
hh:mm
616
Standard values
NO
Holidays HC1
Parameter
Function
Factory settings
Min.
Max.
Units
641
Preset
1
8
-
642
Start
-
01.01
31.12.
dd.MM
643
End
-
01.01
31.12.
dd.MM
648
Type of operation
Anti-frost protection
Anti-frost protection,
Setback
hh:mm
Holidays
the selected operating mode for heating for a long period. The function is activated by the date set
in parameter 642 and ends at 00:00 of the date set in the parameter 643.
Holidays HC2 (only if activated)
Parameter
Function
Factory settings
Min.
Max.
Units
651
Preset
1
8
-
652
Start
-
01.01
31.12.
dd.MM
653
End
-
01.01
31.12.
dd.MM
658
Type of operation
Anti-frost protection
Anti-frost protection,
Setback
hh:mm
Holidays HC3 (only if activated)
Parameter
Function
Factory settings
Min.
Max.
Units
661
Preset
1
8
-
662
Start
-
01.01
31.12.
dd.MM
663
End
-
01.01
31.12.
dd.MM
668
Type of operation
Anti-frost protection
Anti-frost protection,
Setback
hh:mm