35
Installing a Vent
Two-pipe sidewall venting
Internal view
Intake air
Exhaust gas
10" min.
External view
12" (300 mm) min.
Intake air
Less than 45°
Exhaust Gas
12" (300 mm) min.
Caution
•
Maintain 12" (300 mm) min. (18" (450 mm) min. for Canada)
clearance above highest-anticipated snow level. Maximum
of 24" (600 mm) above roof.
•
Install a bird screen at the end of the intake air pipe and
exhaust pipe.
Notice
It is recommended to install the intake air vent terminal as far from the
exhaust gas vent terminal as possible.
Snorkel flue
10" (254 mm) min.
12" (300 mm) min.
12" (300 mm) min.
Schedule 40 PVC pipe
Caution
•
Maintain 12" (300 mm) min. (18" (450 mm) min. for Canada)
clearance above highest-anticipated snow level. Maximum
of 24" (600 mm) above roof.
•
Install a bird screen at the end of the intake air pipe and
exhaust pipe.