47
Operating the Boiler
Setting the Heat Load for The
Outdoor Reset Control Mode
•
Move No. 2 PCB DIP switch in the ON direction.
1 2 3 4 5 6 7 8
ON
•
Press the MODE and buttons for 5 seconds. The outdoor
reset lamp will turn on, and C7 and ON or OFF will be displayed
repeatedly on the screen.
•
At this time, you can set ON or OFF using the or button.
C7 : ON = The boiler operates in outdoor reset mode using the
ambient temperature sensor.
C7 : OFF = The boiler operates according to the heating water
temperature.
•
When you set ON for C7 and press the MODE button, C8 and “1”
will be displayed repeatedly.
•
You can set a value from 0 to 6 using the and buttons.
(The factory default value is 1.)
The meaning of each number is as follows.
Outdoor reset heat load types
0: Finned tube heat load types
1: Fan coil
2: Cast iron baseboard
3: Low mass radiant
4: High mass radiant
5: Radiator
6: Custom
The set temperature for each heat load type is as follows.
Heat load
Minimum
set-point
Maximum
set-point
Out temperature
Min-maximum
Finned
tube heat
load types
118°F(48°C)
180°F(82°C)
Minimum out
temperature: 14°F(-10°C)
Maximum out
temperature: 68°F(20°C)
Fan coil
120°F(60°C)
180°F(82°C)
Cast iron
baseboard
100°F(38°C)
170°F(77°C)
Low mass
radiant
82°F(28°C)
140°F(60°C)
High mass
radiant
82°F(28°C)
122°F(50°C)
Radiator
118°F(48°C)
170°F(77°C)
Custom
User define