52
Installation Manual
15
Set the DIP switch to maximum heat capacity operation.
Danger
Be sure to turn off the power before changing the DIP
switch setting.
Notice
For more information about setting the DIP switches, refer to
"Setting the DIP Switches" on page 37.
16
Fully open several hot water fixtures and if the CO
2
value at
high fire is not within 0.5% of the value listed in the table
above, do not adjust the gas valve set screw and check if the
gas orifice is properly installed.
Danger
Improper gas valve settings can cause severe injury,
death or property damage.
Notice
While measuring the gas/air ratio in maximum heat capacity
operation, do not adjust the gas valve set screw.