Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
168
REPORT ALARM
(REPT ALM {EQPT/COM})
Referenced In: TR-NWT-000833, Issue 5; pg. 5-5
General Description: Generated by an NE (monitor unit) to report the occurrence of alarmed events. Trouble
events occurring in the NE (monitor unit) are classified as alarmed or non-alarmed events.
Message Format:
cr lf lf
^^^<source identifier>^<date>^<time> cr lf
<almcde>^<atag>^REPT^ALM^EQPT
cr lf <rspblk> cr lf;
NOTE!
The only second message modifier supported for this monitor unit application is ‘EQPT’. Other
message modifiers allowed by the TL1 protocol standards are not supported.
<rspblk>
This is the response block which may be repeated multiple times.
^^^”<aid>:<ntfcncde>,<condtype>,<srveff>, [<ocrdat>],[<ocrtm>],[<locn>],[<dirn>],
[<monval>],[<thlev>][,<tmper>] [:[<conddescr>],[<aiddet>][,<obsdbhvr>[,<exptdbhvr>]]
[:[<dgntype>][,<tblistl>]]]”
In this application each individual response block specifies only one alarm. Use of multiple values
for parameters (referred to as parameter grouping) in the response block is not supported.
<aid>
Identifies the single entity in the NE (monitor unit) to which the alarm pertains.
<ntfcncde>
This is the notification code associated with a single alarm condition given in this block. Valid
values are as follows:
CR
Critical alarm
MJ
Major alarm
MN
Minor alarm
CL
Cleared alarm
For this application, values are derived from the
notification code
configuration parameter of the
monitor unit configuration with which the alarm condition is associated. The exception to this is the
CL code which is used when reporting an alarm has cleared.
<condtype>
This is the condition type of the alarm. It indicates the type of failure that has occurred/cleared.