Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
139
-- 6302.4.1.2.4 Distribution devices values { sys 4 }
------------------------------------------------------------
device OBJECT IDENTIFIER ::= { sys 4 }
deviceTable OBJECT-TYPE
SYNTAX SEQUENCE OF DeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device Table."
::= { device 1 }
deviceEntry OBJECT-TYPE
SYNTAX DeviceEntry
MAX-ACCESS not-accessible
STATUS current
DESCRIPTION
"Device Table Entry."
INDEX { deviceIndex }
::= { deviceTable 1 }
DeviceEntry ::= SEQUENCE {
deviceIndex
Integer32,
devicePanel
panelPositionString,
deviceID
Integer32,
deviceName
DisplayString,
deviceExists
EnableState,
deviceTotalCurrent
Integer32,
deviceTotalPower
Integer32,
devicePeakPowerLast24hrs
Integer32,
devicePeakPowerLastWeek
Integer32,
devicePeakPowerLastMonth
Integer32,
deviceTotalEnergyLast24hrs Integer32,
deviceTotalEnergyLastWeek Integer32,
deviceTotalEnergyLastMonth Integer32,
deviceTotalEnergy
Integer32,
deviceFACBStatus
FACBState,
deviceClearAccumulatedValues ClearDataOptions,
deviceCurrentBreakerSize
Integer32,
deviceHighCurrentLimit1
Integer32,
deviceHighCurrentLimit2
Integer32,
deviceNumberofBreakerPositions DeviceNumberofBreaker
}
deviceIndex OBJECT-TYPE
SYNTAX
Integer32(1..320)
MAX-ACCESS read-only
STATUS current
DESCRIPTION
"Automatically generated index object"
::= { deviceEntry 1 }
devicePanel OBJECT-TYPE
SYNTAX panelPositionString
MAX-ACCESS read-only
STATUS current
DESCRIPTION "
The panel containing this device (A=1, B=2, etc.)."
::= { deviceEntry 2 }
deviceID OBJECT-TYPE