Vertiv
|
NetSure Monitor Unit User Manual (UM1M832DNA)
|
Rev. C
14
Using the Web Interface
Overview
Via the Web Interface, a User (with proper access level) can:
•
View real-time operating information.
•
View and download information recorded in logs.
•
Send control commands.
•
Set programmable parameters.
•
Download and upload configuration package.
•
Download firmware to the monitor unit.
Multiple Browsers Supported
Multiple browsers are supported in the Web Interface. The User can use Internet Explorer, Chrome, Safari, or
Firefox.
Web Interface Screens
Refer to “Web Interface Screens” on page 52.
Procedures
Setting IPv4 Communications Parameters (if monitor unit not set as DHCP)
The monitor unit’s IPv4 parameters (IP, subnet mask, and gateway addresses) must be set to match your
company’s network settings. The default settings for these parameters are shown below.
•
IP Address: 192.168.1.2
•
Subnet Mask Address: 255.255.255.0
•
Gateway Address: 192.168.1.1
Local Menu Navigation:
Main Menu / Settings Icon / Comm Settings / enter parameters.
Web Menu Navigation:
Advance Settings Menu / Ethernet Tab / enter parameters.
Setting IPv6 Communications Parameters (if monitor unit not set as DHCPv6)
The monitor unit’s IPv6 parameters (IPv6 address, IPv6 prefix, and IPv6 gateway address) must be set to match
your company’s network settings. The default settings for these parameters are shown below.
•
Link-Local Address: fe80:209:f5ff:fe09:1002/64
•
IPv6 Address: 20fa:fffd:fffc:fffb:fffa:fff9:fff8:fff7
•
IPv6 Prefix: 0
•
IPv6 Gateway: 20fa:1:fffe:ffff:fffe:fffd:ffff:fffe